Cycles of concentration (COC) are the number of times the salts in the make-up water are concentrated inside the cooling tower, calculated by dividing the tower water conductivity by the make-up water conductivity. The higher the cycles, the lower the blowdown and the consumption of water and chemicals, but the greater the risk of scale and corrosion. Setting them at the highest safe value is the most important operating decision in a tower treatment program.
How are cycles of concentration calculated?
Cycles of concentration = tower water conductivity ÷ make-up water conductivity
Example: the make-up water has a conductivity of 500 µS/cm and the tower water 2000, so the cycles = 4. Chlorides can be used instead of conductivity as a cross-check, because chloride does not precipitate and is not affected by the chemicals added (unless chlorine is used heavily).
How are evaporation, blowdown and make-up related?
- Make-up = evaporation + blowdown + drift loss
- Blowdown = evaporation ÷ (cycles of concentration − 1) (ignoring drift, because it is small)
- Make-up = evaporation × cycles of concentration ÷ (cycles of concentration − 1)
Evaporation is set by the heat load, not by the treatment program. As a rule of thumb, about 1% of the circulation rate evaporates for every 5.5–6 °C of temperature difference between the water entering and the water leaving the tower.
Worked example: what changes when the cycles are raised?
A tower evaporating 10 m³/h:
| Cycles of concentration | Blowdown (m³/h) | Make-up (m³/h) | Make-up saving compared with 2 cycles |
|---|---|---|---|
| 2 | 10.0 | 20.0 | — |
| 3 | 5.0 | 15.0 | 25% |
| 4 | 3.3 | 13.3 | 33% |
| 5 | 2.5 | 12.5 | 37.5% |
| 6 | 2.0 | 12.0 | 40% |
| 8 | 1.4 | 11.4 | 43% |
The table shows that the biggest saving comes from moving from two cycles to four or five, and that beyond about six cycles the extra saving becomes small against a clear rise in the risk of scale. The chemicals follow the blowdown: every cubic metre blown down carries with it inhibitor that has been paid for.
What sets the maximum safe cycles?
- Calcium hardness and alkalinity in the make-up water: the first factor in the risk of calcium carbonate scale.
- Silica: it has a solubility limit that is difficult to exceed without hard scale forming.
- Chlorides and sulphates: they raise the risk of corrosion, especially with stainless steel.
- The capability of the scale and corrosion inhibitor: such as Aqua-CT 101; every program has limits it can tolerate.
- The temperature of the heat-exchange surfaces and the system materials.
The target cycles are therefore calculated from the make-up water analysis, and differ from one site to another.
How do you raise the cycles safely?
- Improving the make-up water: full or partial softening allows higher cycles.
- A suitable inhibitor program and a steady dose with a dosing pump.
- Automatic blowdown by conductivity instead of intermittent manual blowdown, to hold a steady value.
- Side-stream filtration to limit suspended solids.
- Monitoring by testing: conductivity daily, and hardness, alkalinity and chlorides weekly with on-site test kits.
Cycles of concentration FAQ
What is the ideal value for cycles of concentration?
There is no single value. Many towers run between 3 and 6 cycles, and the right value for your tower is calculated from the make-up water analysis.
Why do the cycles drop suddenly?
Usually because of a water loss that is not accounted for: a leak, the basin overflowing, a blowdown valve that does not close, or tower water being drawn off for another use.
And why do they rise above the limit?
Blowdown that is insufficient or blocked, or a change in the make-up water. A sustained rise means scale is on its way.
Are cycles calculated from conductivity always accurate?
They are adequate for daily operation. If they differ widely from the cycles calculated from chlorides or from hardness, this may indicate salts depositing inside the system.
Summary
One number that you follow every day sums up a cooling tower’s efficiency in water and chemicals. Read the cooling tower water treatment guide, or learn about Aqua System’s treatment and follow-up service.