Technical Guides

Cooling Tower Water Treatment: Controlling Scale, Corrosion and Algae

A cooling tower concentrates salts with every litre it evaporates. We explain the four cooling-water problems, cycles of concentration and blowdown, and what a chemical program and routine testing should include.

  • 10 November 2026
  • 5 min read

Cooling tower water treatment is a program that combines specialised chemicals (a scale and corrosion inhibitor and biocides) with blowdown control and routine testing, to manage four problems caused by evaporation and the concentration of dissolved salts: scale, corrosion, biological growth and suspended solids. The aim is to keep cooling efficiency and equipment life with the lowest practical use of water and chemicals.

Why does water quality change inside a cooling tower?

A cooling tower cools water by evaporating part of it. The evaporated water leaves as pure vapour and its salts stay in the basin, so hardness, alkalinity, chlorides and silica rise with every cycle. At the same time the tower scrubs the air passing through it, picking up dust, organic matter and micro-organisms. The result is warm, oxygen-saturated, concentrated water: ideal conditions for scale, corrosion, algae and bacteria.

What are the four cooling tower water problems?

Problem Cause Effect on the system Control
Scale Hardness and alkalinity concentrating at higher temperature Insulated exchanger and condenser surfaces, higher energy use Scale inhibitor + blowdown control + make-up softening where needed
Corrosion Dissolved oxygen, chlorides, low pH Attack on pipework, exchangers and the tower structure; leaks Corrosion inhibitor and water chemistry control
Biological growth Warm water, nutrients and sunlight Algae and slime blocking the fill; health risks such as Legionella Two alternating biocides + a clean basin
Suspended solids Airborne dust and corrosion products Blocked nozzles and fill, under-deposit corrosion Dispersants + side-stream filtration + periodic cleaning

What are cycles of concentration, and why control blowdown?

Cycles of concentration are the ratio of dissolved salts in the tower water to those in the make-up water; in practice they are found by dividing tower-water conductivity by make-up conductivity. Higher cycles save water and chemicals, but raise the risk of scale and corrosion.

Blowdown removes part of the concentrated water and replaces it with fresh make-up, keeping the cycles at the limit the system can tolerate. That limit is not arbitrary: it is calculated from the make-up water analysis and the capability of the chemical program. Too much blowdown wastes water and chemicals; too little causes scale.

What does a cooling tower treatment program include?

  1. Analysis of make-up and tower water: hardness, alkalinity, chlorides, conductivity and pH — the basis of program design.
  2. Scale and corrosion inhibitor: such as Aqua-CT 101, dosed by pump to hold a steady level.
  3. Alternating biocides: such as AquaB1 and AquaB2; alternating two different biocides widens the spectrum and reduces the chance of micro-organisms adapting.
  4. Blowdown control: manual, or automatic with a conductivity controller.
  5. Make-up pre-treatment where needed: a softener or filtration when the water is hard or turbid.
  6. Mechanical cleanliness: regular cleaning of the basin, fill and strainers; chemicals do not replace cleaning.

Which routine tests does tower water need?

  • Conductivity: to calculate cycles of concentration and set blowdown.
  • pH and alkalinity: they decide whether the water tends to scale or corrode.
  • Total and calcium hardness: a direct indicator of scaling risk.
  • Chlorides: high levels increase corrosion risk, especially on stainless steel.
  • Inhibitor level: to confirm the dose is effective.
  • Biological monitoring: bacterial counts and visual checks for algae and slime.

Most of these are measured on site with water test kits. For details see our guide to boiler, cooling tower and chiller water analysis.

Cooling tower treatment FAQ

Is chlorine alone enough to treat a cooling tower?

No. Chlorine controls biological growth only; it does not prevent scale or corrosion, and overdosing can increase corrosion. A tower needs a scale and corrosion inhibitor alongside the biocide program.

Why does scale appear even though a scale inhibitor is used?

Usually because cycles of concentration are above the calculated limit (not enough blowdown), the inhibitor dose has dropped, or the make-up water quality has changed. Routine testing shows which.

Does a softener help a cooling tower?

When make-up water is very hard, softening it allows higher cycles and saves water. Softened water needs closer attention to corrosion inhibition, so the decision is made after a water analysis.

How often should a cooling tower be cleaned?

It depends on site conditions and dust. Common practice is regular visual inspection of the basin and fill, a periodic full clean with disinfection, and immediate cleaning when algae or slime appear.

Summary

Controlling cooling tower water is a balance between chemicals, blowdown, cleanliness and testing; if one slips, scale, corrosion or algae follow. Learn about our boiler, cooling tower and chiller water treatment service, browse cooling tower chemicals, or read about chiller water treatment.

Want your treatment program reviewed? Contact the Aqua System technical team and send your water analysis if you have one — we will come back with a suitable program and a clear quotation.

Keep reading

Related articles

Talk to an engineer

Need a water treatment solution that fits your facility?

Send your water analysis or describe your current system, and our technical team will come back with a clear, suitable proposal.

Chat with us on WhatsApp (opens WhatsApp)